Model |
NP100 |
NP200 |
Appearance |
|
|
W × H × D (mm) |
96 × 96 × 100 |
Function |
ㆍRetransmission output ㆍInput correction ㆍAuto/Manul output ㆍHeating/Cooling Control |
ㆍ2 Alarm output (Relay) |
ㆍ2 TIme signals (Transistor) |
|
ㆍConstant-value control |
ㆍ5 Inner signals |
ㆍZone PID |
ㆍ5 Time signals |
|
Power voltage |
100 - 240 V a.c (50/60 ㎐) |
Power consumption |
Max. 10 VA (except communication) |
Input |
Multi input (T.C : 13 kinds, R.T.D : 2 kinds, Voltage : 5 kinds) |
Control output |
Universal-output : Relay, SSR, Current |
Control action |
P.I.D or ON/OFF |
Alarm |
2 Alarm output |
4 Alarm output |
Communication |
RS 485/422 (Optional) |
Setting |
By Up/Down key on the front |
Display |
PV / SV : Digital LED |
PV : Digital LED , SV : LCD Back light |
Setting and display accuracy |
0.1 % of F.S (Full Scale) |
Setting resolution |
1 or 0.1% (According to input range) |
Memory protection |
Semipermanent |
External control |
3 Alarm output (Run, Reset, Hold) |
4 Alarm output (Run, Reset, Step, Hold) |
Number of pattern |
2 |
30 |
Number of segment |
20 |
300 |
Number of pattern contact |
- |
30 |
Operation |
1 ~ 99 times or limitless |
Program inclination |
Hour, Minute |
Sampling cycle |
250 ms |
Insulation resistance |
500 V a.c 20 ㏁ min. |
Dielectric strength |
2300 V a.c 50/60 ㎐ for 1 minute
(Between primary and secondary terminal & between primary and ground) |
Ambient temperature & humidity |
0 ~ 50 ˚C (Between primary and ground), 20 ~ 90% R.H. |